Siemens RDG 200T

Code: RDG200T
Not rated Rating details
202,80 € –10 %
A6V14139246
202,80 € –10 % 182,50 € / pcs Measure price:
In stock now (1 pcs)

Detailed information

Product detailed description

Temperature controller for fan coil units, 4 triac outputs Y, 3 relay outputs Q, 1 DC 0 - 10 V output for fan, AC 230 V power supply

  • Built-in temperature sensor 
  • For applications with 2-point (on/off or PWM) or 3-point control outputs
  • For applications with a 3-speed or DC 0...10 V fan
  • Operating modes: Comfort, Setback and Protection mode
  • Automatic or manual control of DC or 1-/3-speed fan
  • Automatic or manual heating/cooling changeover
  • Limitation of maximum and minimum adjustable setpoint temperature
  • Backlit display
  • Weekly time program (3 Comfort time blocks per day)
  • Clock backup during power failure
  • Commissioning possible using the "PCT Go" mobile app
  • Supply voltage AC 230 V

Optional applications:
2-pipe system
2-pipe system with electric heating
2-pipe system and radiator / underfloor heating
2-pipe / 2-stage heating or cooling system
4-pipe system
4-pipe system with electric heating

Operating voltage AC 230 V
Power consumption  7 VA
Setting range    5…40 °C
Sensing element   NTC 3k
Switching differential   Heating: 0.5…6 K; Cooling: 0.5…6 K
Analog inputs, number 3
Analog outputs 1x Fan (DC 0...10 V)
Analog outputs, number 1
Analog outputs, signal DC 0...10 V
Analog output, current 1 mA
Digital inputs, number 3
Relay outputs 1-speed or 3-speed fan
Relay outputs, number 3
Relay output, switching voltage AC 230 V
Relay output switching current 5 (4)A
Triac outputs Valves, electric heating, 2-point, PWM, 3-point
Triac outputs, number 3
Triac output, switching voltage AC 230 V
Triac output, switching current 1 A
Mounting type Wall mounting with screws
Degree of protection IP30
Dimensions (W x H x D) 92 x 134 x 25 mm
Colour White

 












Frequently asked questions

  • How exactly does a manual (simple) thermostat work? It measures the temperature at its installation location and, when it drops below the set value, closes a contact that starts the heat source (boiler, pump, heating appliance) - once the set temperature is reached, the contact opens again. Unlike programmable thermostats, it has no weekly or daily program; the temperature is set manually using a rotary or slide control.
  • Where should the thermostat be placed? In a location that best represents the typical room temperature - away from direct sunlight, draughts, radiators or other heat/cold sources that could distort the measurement.
  • Must the installation be carried out by an electrician? Connecting the thermostat to the electrical circuit of the heat source should be carried out by a person with electrical qualification, as it involves work on the electrical installation and load switching.

Additional parameters

Category: fan-coil controls
Warranty: 2 years
AC supply voltage: 230 V

Product rating

Be the first who will post an article to this item!

Do not fill out this field:

How would you rate this product? Choose 1 to 5 stars, where 1 is the worst and 5 is the best rating.

Discussion

Be the first who will post an article to this item!

Do not fill out this field:
Vytvořil Shoptet | Design Shoptak.cz. > >